![Pollution Pollution](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/picto1.gif)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![Humain Humain](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/picto2.gif)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![Environnement Environnement](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/picto3.gif)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![Economique Economique](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/picto4.gif)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
![](https://www.aria.developpement-durable.gouv.fr/wp-content/themes/Total/library/images/recherche/note-vide.png)
The summary of this accident has not yet been translated. In the meantime, please refer to the French summary :
Vers 19H15, un riverain appelle les pompiers après avoir vu des fumées noires s’échappant d’un site agroalimentaire. Le cadre d’astreinte contacte un technicien habitant à proximité du site, qui arrive peu de temps après les pompiers. Le panache provient du local où se trouve le tableau général basse tension (TGBT). L’incendie est rapidement circonscrit au moyen d’un extincteur à CO2. L’armoire est déconnectée et transportée hors du local ; ce dernier est ventilé.
Le départ de feu est lié à un défaut sur le condensateur à avance de phase basse tension. Ce condensateur, âgé de 20 ans, avait fait l’objet d’une vérification thermique lors du contrôle annuel 7 mois avant les faits.
À la suite de l’événement, l’exploitant décide de :
- réviser ses procédures d’information en externe ;
- vérifier dans toutes les armoires électriques la présence de condensateurs à avance de phase basse tension et l’âge de ces condensateurs ;
- remplacer les condensateurs de plus de 10 ans ;
- implanter les nouvelles batteries en dehors du TGBT afin de limiter le risque de propagation d’incendie ;
- modifier la fréquence d’inspection de toutes les armoires d’alimentation électrique d’une fois par an à deux fois par an;
- faire un retour d’expérience et une sensibilisation des équipes afin de prévenir un nouvel incident.